Cisco ONS 15454 M6 - DLP-G572 Connect Office Power (DC) to the ONS 15454 M6 Shelf (ANSI Only)

Cisco ONS 15454 M6
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PIDCable
15454-M-CBL-LARG=AC power cable - ARG left exit
15454-M-CBL-RARG=AC power cable - ARG right exit
15454-M-CBL-LAUS=AC power cable - AUS left exit
15454-M-CBL-RAUS=AC power cable - AUS right exit
15454-M-CBL-L-UK=AC power cable - UK left exit
15454-M-CBL-R-UK=AC power cable - UK right exit
15454-M-CBL-LKOR=AC power cable - KOR left exit
15454-M-CBL-RKOR=AC power cable - KOR right exit
15454-M-ACCBL-L=AC power cable ANSI 110VAC left exit
15454-M-ACCBL-R=AC power cable ANSI 110VAC right exit
15454-M-ACCBL-L2=AC power cable ANSI 220VAC left exit
15454-M-ACCBL-R2=AC power cable ANSI 220VAC right exit
15454-M-ACL6-L=AC power cable for data center left exit
15454-M-ACL6-R=AC power cable for data center right exit
DLP-G572 Connect Office Power (DC) to the ONS 15454 M6 Shelf (ANSI Only)
This task connects DC power to the ONS 15454 M6 (ANSI Only).Purpose
#2 Phillips Dynamometric screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Wire wrapper
Wire cutters
Wire strippers
Crimp tool
Open-end wrench or hex tube screw driver
Fuse panel
Power cable (from fuse and alarm panel to assembly), #8 AWG, copper
conductors, 194 degrees F (90 degrees C)
Ground cable #6 AWG stranded
Listed pressure dual-holes lugs suitable for #8 AWG copper conductors
Tools/Equipment
Installing the ONS 15454 M6 Shelf
107
Installing the ONS 15454 M6 Shelf
DLP-G572 Connect Office Power (DC) to the ONS 15454 M6 Shelf (ANSI Only)

Table of Contents

Related product manuals