OnsiteOnsite/Remote
NoneSecurity Level
Always use the supplied ESD wristband when working with a powered ONS 15454 M6. For detailed instructions
on how to wear the ESD wristband, see the Electrostatic Discharge and Grounding Guide for Cisco CPT and
Cisco ONS Platforms.
Caution
Procedure
Step 1 Complete the DLP-G295 Install Alarm Wires in ONS 15454 M6, on page 128 if you are provisioning external
alarms.
Step 2 Complete the DLP-G296 Install Timing Wires on ONS 15454 M6 - ANSI, on page 133 if you are provisioning
external timing in ANSI.
Step 3 Complete the DLP-297 Install Timing Wires in ONS 15454 M6 - ETSI, on page 134 if you are provisioning
external timing in ETSI.
Step 4 Complete the DLP-G298 Install LAN Wires in ONS 15454 M6, on page 136 to create an external LAN
connection.
Stop. You have completed this procedure.
Table 4: PIDs for SCSI Cables
Wire DimensionLengthPIDCable
28 AWG20 Meter15454-M-ALMCBL=SCSI alarm cable
28 AWG1 Meter15454-M-AEXPCBL=SCSI alarm patch cable
24 AWG20 Meter15454-M-ALMCBL2=SCSI alarm wire-wrap cable
Some wire-wrap tools require a minimum of 24 AWG wires to prevent breakage. Ensure that the
SCSI alarm wire-wrap cable is used for 24 AWG wires. When the SCSI alarm wire-wrap cable is
used, the number of alarms is reduced as fewer strands of wire are supported compared to the SCSI
alarm and SCSI alarm patch cables. Table 6: SCSI Alarm Wire-Wrap Cable (15454-M-ALMCBL2)
Connector Details , on page 131 lists alarm connector pin details for SCSI alarm wire-wrap cable.
Note
DLP-G295 Install Alarm Wires in ONS 15454 M6
This task installs alarm cables on the ECU module of the ONS 15454 M6 to
provision external (environmental) alarms and controls.
Purpose
Installing the ONS 15454 M6 Shelf
128
Installing the ONS 15454 M6 Shelf
DLP-G295 Install Alarm Wires in ONS 15454 M6