Step 9 Return to your originating procedure (NTP).
DLP-G738 Replacing 15454-M6-DC20 With 15454-M6-DC Power Module
This procedure replaces the 15454-M6-DC20 with 15454-M6-DC power module.Purpose
#2 Phillips Dynamometric screwdriverTools/Equipment
NTP-G259 Open and Remove the Standard Door of the ONS 15454 M6 Shelf ,
on page 57.
Prerequisite Procedures
RequiredRequired/As Needed
OnsiteOnsite/Remote
NoneSecurity Level
The procedure to replace the 15454-M6-DC20 power module with 15454-M6-DC40 power module is the
same as this procedure. The 15454-M6-DC40 power module uses 15454-M6-DCCBL2-L= and
15454-M6-DCCBL2-R= cables.
Note
While changing the power modules from 15454-M6-DC20 to 15454-M6-DC and vice-versa, the ONS 15454
M6 shelf can temporarily work with both 15454-M6-DC and 15454-M6-DC20 power modules installed.
However, during regular operation, the shelf must either have the 15454-M6-DC or 15454-M6-DC20 power
module, but not both.
Caution
Always use the supplied ESD wristband when working with a powered ONS 15454 M6. For detailed instructions
on how to wear the ESD wristband, see the Electrostatic Discharge and Grounding Guide for Cisco CPT and
Cisco ONS Platforms .
Caution
Procedure
Step 1 Disconnect the power source and remove the power connections from the standby power module (installed
in slot B).
Step 2 Unscrew the holding screw that secures the 15454-M6-DC20 power module.
Step 3 Pull the 15454-M6-DC20 power module clear from the ONS 15454 M6 chassis.
Step 4 Install the 15454-M6-DC power module as described in the DLP-G570 Install the DC Power Module in the
ONS 15454 M6 Shelf, on page 90.
Step 5 Install power on the 15454-M6-DC power module as described in the NTP-G256 Install Power and Ground
to the ONS 15454 M6 Shelf , on page 100.
Installing the ONS 15454 M6 Shelf
95
Installing the ONS 15454 M6 Shelf
DLP-G738 Replacing 15454-M6-DC20 With 15454-M6-DC Power Module