Figure 15: Installing the right vertical air plenum
Step 7 Place the horizontal air plenum above the shelf slot in the ANSI 23-inch cabinet or rack.
Step 8 Install the wing head screws provided with the kit, and tighten to a torque value of 11.5 in-lb (1.3 N-m).
Figure 16: Installing the horizontal plenum above the vertical plenums
Step 9 Install ANSI 23-inch standard brackets on both sides of the chassis in front position. See DLP-G562 Mounting
the Brackets on the ONS 15454 M6 Shelf for ETSI Rack Configuration, on page 34.
Step 10 Check the length between the top and bottom horizontal air plenums where the chassis will be installed. The
length must be not less than 10.5 inches (267 mm). If the length is less, adjust the position of the top horizontal
plenum.
Step 11 Install the ONS 15454 M6 empty chassis between the horizontal plenums.
Installing the ONS 15454 M6 Shelf
16
Installing the ONS 15454 M6 Shelf
DLP-G767 Install Air Plenum in ONS 15454 M6 Shelf for ANSI 23-inch Configuration