2-4
Cisco UCS C460 Server Installation and Service Guide
OL-22326-01
Chapter 2 Installing the Server
Preparing for Server Installation
Rack Requirements
This section provides the requirements for the standard open racks, assuming an external ambient air
temperature range of 32
F to 95F (0C to 35C).
The rack must be of the following type:
A standard 19-in. (48.3-cm) wide, four-post EIA rack, with mounting posts that conform to English
universal hole spacing, per section 1 of ANSI/EIA-310-D-1992.
The rack post holes must be square when you use the supplied slide rails.
The minimum vertical rack space per server must be four RUs, equal to 7 in. (17.8 cm).
Tip The Cisco R-Series racks and RP-Series PDUs have been designed for optimum performance with Cisco
products and are available from Cisco.
Equipment Requirements
The slide rails supplied by Cisco Systems do not require any tools for installation, but you might want
to use a tape measure and level to help level the slide rails during installation.
Slide Rail Adjustment Range
The slide rails for this server have an adjustment range of 26 to 36 inches (660 to 914 mm).

Table of Contents

Other manuals for Cisco UCS C460

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco UCS C460 and is the answer not in the manual?

Cisco UCS C460 Specifications

General IconGeneral
BrandCisco
ModelUCS C460
CategoryServer
LanguageEnglish

Related product manuals