ECON-4 1.4.0 Global Guide
63
Setpoint group Main PID Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0.0 – 100.0 %
Default value 100% Force value NO
Step 0.1 %
Comm object 7184 Related applications ALL
Setpoint visibility Always
Description
Maximum output from the PID speed control loop + Load anticipation signal. It limits the maximum fuel
delivered to the engine.
MaxFuel
Note: It is also used as coordinate for Speed/Fuel line. See description in chapter Speed governor function in
parallel mode.
6 back to List of setpoints
Setpoint group Main PID Related FW
1.4.0
configured ECON-4 extension
module
Range [units] 0.0 – 100.0 %
Default value 10% Force value NO
Step 0.1 %
Comm object 7192 Related applications ALL
Setpoint visibility Always
Description
IdleFuel is base (together with MaxFuel) for Droop function calculation..
IdleFuel
Note: Set this setpoint after engine is running on Nominal speed (no load) according to the real position of
Actuator lever
6 back to List of setpoints