InteliMains
NT
, SW version 3.0  
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013   
14.2.1.19  Binary input: ManualLdRecon 
This input is used for manual reconnection of the last disconnected part of 
the load, if the load has dropped below the setpoint Ld recon level. 
This input works only if automatic reconnection is disabled, i.e. the setpoint 
AutoLd recon is set to DISABLED. 
 
14.2.1.20  Binary input: FaultResButton 
This input is used for an external FAULT RESET button mounted on the 
switchboard. The function of the input is identical as function of the fault reset 
button on the controller front panel. 
The input is enabled only if the setpoint Local Button is set to position 
EXTBUTTONS or BOTH. 
 
14.2.1.21  Binary input: HornResButton 
This input is used for an external HORN RESET button mounted on the 
switchboard. The function of the input is identical as function of the horn reset 
button on the controller front panel. 
The input is enabled only if the setpoint Local Button is set to position 
EXTBUTTONS or BOTH. 
 
14.2.1.22  Binary input: BTBButton 
This input is used for an external BTB button mounted on the switchboard. 
The function of the input is identical as function of the BTB button on the 
controller front panel. 
The input is enabled only if the setpoint Local Button is set to position 
EXTBUTTONS or BOTH. 
 
14.2.1.23  Binary input: GroupLink