InteliMains 210 Global Guide
176
Setpoint group Basic settings Related FW 2.0.0
Range [units] 1 .. 2 000 [A/5A]
Default value 500 A/5A Alternative config NO
Step 1 A/5A
Comm object 8274 Related applications MCB, MGCB, BTB
Description
Bus current transformers ratio.
Note: Generator currents and power measurement is suppressed if current level is below 1% of CT
range.
Bus Import CT Ratio
6 back to List of setpoints
Subgroup: Voltage settings
Setpoint group Basic settings Related FW 2.0.0
Range [units] Mono Phase / SplitPhase / 3Ph3Wire / High Leg D / 3Ph4Wire [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 11628 Related applications MCB, MGCB
Description
Connection type:
Mono Phase Single phase voltage measurement L1-N
1x CT (Current Transformer)
Split Phase Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
High Leg D High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
3Ph4Wire Grounded Star (Grounded Wye) connection – 3PY
Three phase voltage measurement L1,L2,L3 with 120° phase shift
Connection type