EasyManuals Logo

ComAp InteliMains 210 BTB User Manual

ComAp InteliMains 210 BTB
576 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #176 background imageLoading...
Page #176 background image
InteliMains 210 Global Guide
176
Setpoint group Basic settings Related FW 2.0.0
Range [units] 1 .. 2 000 [A/5A]
Default value 500 A/5A Alternative config NO
Step 1 A/5A
Comm object 8274 Related applications MCB, MGCB, BTB
Description
Bus current transformers ratio.
Note: Generator currents and power measurement is suppressed if current level is below 1% of CT
range.
Bus Import CT Ratio
6 back to List of setpoints
Subgroup: Voltage settings
Setpoint group Basic settings Related FW 2.0.0
Range [units] Mono Phase / SplitPhase / 3Ph3Wire / High Leg D / 3Ph4Wire [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 11628 Related applications MCB, MGCB
Description
Connection type:
Mono Phase Single phase voltage measurement L1-N
1x CT (Current Transformer)
Split Phase Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
High Leg D High Leg Delta connection
Three phase voltage measurement L1,L2,L3
3x CT (Current Transformer)
3Ph4Wire Grounded Star (Grounded Wye) connection – 3PY
Three phase voltage measurement L1,L2,L3 with 120° phase shift
Connection type

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals