InteliMains 210 Global Guide
433
Related FW 2.0.0 Related applications MCB, MGCB
Comm object 38
Description
Use this input to start and stop the gen-set in AUTO mode and TEST mode.
Taken action in MCB, MGCB application (AUTO Mode)
Active
System Start/Stop is activated regardless the Mains is OK
MGCB is closed in case of MGCB application
Parallel operation - Baseload, import/export
Reverse synchronising in case of mains return
Inactive
System Start/Stop deactivated
MGCB opened
Note: In the SPTM and AMF application there are more LBIs that can influence the state of the
application and can be in the collision with the Common LBI Remote Start/Stop.
Note: This function is not supported in BTB application.
Remote Start/Stop
6 back to Logical binary inputs alphabetically
LBI: T
Related FW 2.0.0 Related applications MCB, MGCB, BTB
Comm object 125
Description
Binary input activates time stamp writing to history depending on Date/Time:Time stamp act and Time
Stamp Per setpoints.
Time Stamp Act
6 back to Logical binary inputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliMains 210 BTB and is the answer not in the manual?

ComAp InteliMains 210 BTB Specifications

General IconGeneral
BrandComAp
ModelInteliMains 210 BTB
CategoryController
LanguageEnglish

Related product manuals