InteliMains 210 Global Guide
510
Alarm Type Other
Alarmlist message Event SMS4 Fail
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
The alarm indicates that there was a request to send an event SMS to telephone
number which is adjusted in setpoint Telephone Number 4 (page 282) and SMS
wasn’t send.
Event SMS4 Fail
6 back to List of alarms level 1
Alarm Type Alarm indication
Alarmlist message Bus CCW Rotation
Alarm evaluated All the time
Related applications MCB, MGCB
Description
The controller detects phase sequence on bus voltage terminals. This protection is
important after controller installation to avoid wrong voltage phase connection.
There is a fixed defined phase sequence in InteliMains 210 controller: T35 = N, T36
= L1, T37 = L2 and T38 = L3. When the phases are connected in a different order,
alarms are detected. This alarm prevent circuit breaker closing.
Bus CCW Rotation
6 back to List of alarms level 1
Alarm Type Alarm indication
Alarmlist message Bus Left CCW Rotation
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
The controller detects phase sequence on Bus Left voltage terminals. This
protection is important after controller installation to avoid wrong voltage phase
connection.
Bus Left CCW Rotation
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn + Name of analog input
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm indicates that value the general analog protection is out of warning
protection limit.
Wrn AIN Prot
6 back to List of alarms level 1