InteliMains 210 Global Guide
511
Alarm Type Warning
Alarmlist message Wrn BadPwrCfg
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm is issued when there is different power format on controller which are
connected via CAN2.
Wrn BadPwrCfg
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn + Name of binary input
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
Binary input also can be adjusted like alarm. In this case message in alarmlist
contains prefix - Wrn and binary input name. This alarm occurs, when appropriate
binary input is active.
Wrn BIN Protection
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn MCB Fail
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm will occur when the BTB FEEDBACK (PAGE 427) input does not match
the expected position given by the BTB CLOSE/OPEN (PAGE 453) output. It stays
active until the mismatch between the output and feedback disappears.
If there was no command issued by the controller and the breaker
(feedback) changes suddenly the position itself, the alarm will be issued
immediately.
The alarm will be also issued, if the breaker does not respond to the close
command within 2 seconds. After this period has elapsed the output BTB
CLOSE/OPEN (PAGE 453) is deactivated again and the next attempt to close
the breaker will occur first after the alarm is reset.
Wrn BTB Fail
6 back to List of alarms level 1