Alarm Type Warning
Alarmlist message Wrn Overload
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
The alarm is issued when the Bus Left power is over the limit for time period longer
than the delay. The following setpoints are related to it:
Overload Wrn (page 185) adjusts the overload limit.
Overload Delay (page 185) Overload Del adjusts the delay.
Wrn Overload
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Synchronization Fail
Alarm evaluated During synchronization
Related applications MCB, MGCB, BTB
Description
This alarm is issued when bus left is synchronizing to the bus right or vice versa,
via BTB and Synchronization Timeout (page 204) gets elapsed.
Synchronization Fail
6 back to List of alarms level 2
Alarm Type Warning
Alarmlist message Bus Measurement Error
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
The alarm is issued when the voltage on the bus is out of limits for 20 seconds
under these conditions:
MCB application:
MCB is closed in AUTO mode
Any GCB in the same control group was closed
MGCB application:
MCB and MGCB are closed in AUTO mode
Any GCB in the same control group was closed. MGCB closing is blocked
BTB application:
BTB feedback was closed in AUTO mode
Any GCB in power management group (on CAN bus) was closed.
BTBclosing is blocked
Bus Measurement Error
6 back to List of alarms level 2