InteliMains 210 Global Guide
513
Other type
Alarm Type History record
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Right phase voltage in phases. The following
setpoints are related to it:
Bus Right Overvoltage (page 182)
Bus Right < > Voltage Delay (page 183)
Note: Alarm is active only in case the setpoint Connection type (page 176) is
set to 3Ph4Wire or MonoPhase.
Bus Right L1 Overvoltage
6 back to List of alarms level 2
Alarm Type History record
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Right phase voltage in phases. The following
setpoints are related to it:
Bus Right Undervoltage (page 183)
Bus Right < > Voltage Delay (page 183)
Note: Alarm is active only in case the setpoint Connection type (page 176) is
set to 3Ph4Wire or MonoPhase.
Bus Right L1 Undervoltage
6 back to List of alarms level 2
Alarm Type History record
Alarmlist message No
Alarm evaluated All the time
Related applications MCB, MGCB, BTB
Description
This alarm evaluates the Bus Right voltage between phases L1 a L2. The following
setpoints are related to it:
Bus Right Overvoltage (page 182)
Bus Right < > Voltage Delay (page 183)
Note: Alarm is active only in case the setpoint Connection type (page 176) is
set to 3Ph3Wire or High Leg D.
Bus Right L1L2 Overvoltage
6 back to List of alarms level 2