5User Instructions for Control Panel M 2.2 User Manual
26
5100606_CFD5000 T - CM2.2_User Manual_T_EN_2023_E
The warning is also added to the Warning list found under: Menu » 1 Fault Alarms
» 2 Warnings.
A warning will remain in the Warnings list until the fault condition is under the
level for warnings.
5.6 Disablements
5.6.1 About Disablements
WARNING!
To secure the functionality of the fire detection system only authorised persons
should be given access to disablement privileges in the system.
It is possible to disable different devices attached to the system, such as detectors,
manual call points, alarm devices, external control devices, and loops.
All disablements are presented in a disablement list.
NOTE!
The yellow Disablements indicator is lit on the control panel when at least one
disablement is activated in the system and remains lit until all disablements are
reconnected.
To perform a disablement you must enter access level 2B or higher.
DANGER!
When a fire detector or zone is disabled, the fire detection system will not be able to
detect any occurring fire in that area. It is therefore important that disablements are
minimized in terms of quantity of disabled units and duration of time.
Hint!
If dual detectors heat/smoke are installed, it is possible to disable only the smoke
detection part of the detector and keep the heat detecting part active or vice versa.
5.6.2 Available Disablements
NOTE!
Disablements of something belonging to a safety critical function is restricted to
timer disablement. This function requires at least access level 2B.
Permanent disablement
The device is permanently disabled until it is manually enabled.
NOTE!
It is possible to limit the disablement time by defining a maximum disablement time
in the configuration program.
5.6.3 Acknowledgement of a New Disablement
Once a new disablement is correctly entered, an acknowledgement is presented on
the control panel. The Disablements indication indicates with steady yellow light.