7Fault codes User Manual
42
5100606_CFD5000 T - CM2.2_User Manual_T_EN_2023_E
Fault Code
Unit or
Module
Cause Remedy Failure classification
215
CHARGING
CURRENT
EXCEEDED
Charger M
The battery connected
to the affected Charger
M is charged with a
higher current than
allowed.
Charge the battery with an
external charger.
Major fault.
217
HIGH
VOLTAGE
PSU1
Charger M
The voltage delivered
from PSU 1 to the
affected Charger M
module is too high.
1. Measure the voltage
from the power source.
If voltage OK,
change module.
If voltage NOT OK,
change or adjust the
DC/DC acc. to data
sheet for the PSU.
2. Contact an authorised
service office.
Major fault.
CS-Loop M
CS-Safety M
CS-Com M
Voltage above 30
VDC in Backbone Bus
(BB) channel 1.
218
HIGH
VOLTAGE
PSU2
Charger M
The voltage delivered
from PSU 2 to the
affected Charger M
module is too high.
1. Measure the voltage
from the power source.
If voltage OK,
change module.
If voltage NOT OK,
change or adjust the
DC/DC acc. to data
sheet for the PSU.
2. Contact an authorised
service office.
Minor fault if power
sources are
redundant and not
from the same
source.
Major fault if power
from the same power
source.
CS-Loop M
CS-Safety M
CS-Com M
Voltage above 30
VDC in Backbone Bus
(BB) channel 2.
219
FUSE FAULT
PSU1
Charger M
The fuse protecting
the PSU 1 voltage
input is broken.
1. Check the fuse.
If fuse OK, change
module.
If fuse NOT OK,
change the fuse (or
change the module if
LRU).
2. Contact an authorised
service office.
Minor fault if power
sources are
redundant and not
from the same
source.
Major fault if power
from the same power
source.
220
FUSE FAULT
PSU2
Charger M
The fuse protecting
the PSU 2 voltage
input is broken.
1. Check the fuse.
If fuse OK, change
module.
If fuse NOT OK,
change the fuse (or
change the module if
LRU).
2. Contact an authorised
service office.
Minor fault if power
sources are
redundant and not
from the same
source.
Major fault if power
from the same power
source.