13
© Control Concepts Inc., 2013
www.ccipower.com 1-800-765-2799
Compact FUSION Installation Manual Revision 3.50.2
This figure shows a three single phase controllers.
Zone 1 is connected from Phase A to Neutral.
Zone 2 is connected from Phase B to Phase C.
Zone 3 is connected from Phase C to Phase A.
The controller is not phase sensitive and any zone can be connected to any two phases. Any or all
zones can be connected from Phase to Neutral.
Note: During operation Zone 1 must have line power “ON” in order for other zones to operate.
3.4.3 Single Phase, Three Zone
100 -2 40 Ref A
Va c
AC /LAC /N
PE GND
Phase A
Phase B
Loa d A2
Load B2
Phase C
Loa d C2
Re f
BC
L
O
A
D
L
O
A
D
L
O
A
D
Neutra l
Line A1
Line B1
Line C1