EasyManua.ls Logo

CPC 485 - Installation Procedure; Set-up; Board and Point Settings; Set Points and Time Delays

Default Icon
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 • Checkit Refrigeration System Monitor (P/N 508-2000) 026-1701 Rev 0 01-05-98
Installation Procedure
1. Remove the sensor from the holding tube on
the vessel.
2. Solder the vessel directly into the refrigera-
tion line, or on a bypass line if the main line
is larger than 1-5/8".
3. After the vessel and refrigeration line have
cooled completely, apply Wakefield Thermal
Joint Compound #120-5 (CPC P/N 020-
7120) or equivalent on the sensor and re-in-
sert the sensor into the holding tube. (If nec-
essary, silicone sealer may be applied to the
end of the sensor after installation to help en-
sure the sensor remains in the holding tube.)
When installed, the sensor should fit com-
pletely within the holding tube.
4. Secure the sensor leads to the refrigeration
line with a standard cable tie located adjacent
to the sensor.
5. The Checkit sensor requires 24 VAC. Con-
nect the sensor leads as follows: (a)Connect
the two black leads to the 24 VAC output on
the 16AI board, as shown in Figure 14, or to
an alternate 24 Volt power source. (b)Con-
nect the two gray leads to an input on the
16AI board (the polarity of each of the leads
is not important). Set the corresponding in-
put’s dip switch to the UP position.
6. Checkit installation is complete.
If a damaged Checkit sensor needs to be replaced, fol-
low the instructions above, skipping Step 2, using a re-
placement sensor (CPC P/N 201-2010).
Set-up
Board and Point Settings
Before monitoring of the Checkit sensor by the RMCC
can begin, the location of the Checkit sensor must be iden-
tified. The following procedure should be used for location
identification:
1. Return to the Main Menu.
2. Select 7) Configuration from the Main Menu.
3. Select 1) Input Definition from the Configu-
ration Menu.
4. Page down the Input Definitions Pages to the
Checkit Page.
5. Input the 16AI board number and point num-
ber for the Checkit sensor.
6. Checkit sensor setup is complete.
Set Points and Time Delays
To configure the RMCC unit for Checkit monitoring,
the following procedure should be followed:
1. Log on the RMCC unit with the proper pass-
word.
2. Select 1) Pressure Control from the Main
Menu.
3. Select 3) Alarms from the Pressure Control
Menu.
4. Page down the Alarms Pages to the Checkit
Page.
Figure 13 - Installation of Checkit and Bypass for Lines Larger
than 1 5/8”
The Checkit sensor assembly may become hot during
the soldering process.
Power to the sensor should be shut-off and the sensor
allowed to cool completely if it becomes necessary to
remove the sensor from the holding tube for inspec-
tion or replacement.
Figure 14 - Checkit Typical Power Connections

Table of Contents

Other manuals for CPC 485