Peripherals Manual Standard Pressure Transducers • 37
Standard Pressure Transducers
0–100 PSIG–P/N 800-0105
0–200 PSIG–P/N 800-0205
0–500 PSIG–P/N 800-0505
Overview
Standard transducers are available as replacements for
BEC, BCU, and RMCC systems.
Table 10 lists the part numbers for the 100, 200, and
500 lb. pressure transducers along with pressure/voltage
ranges for each CPC standard pressure transducer type.
Description
Computer Process Controls pressure transducer is a
pressure sensing device that converts pressure readings to
a proportional electrical signal between one and six volts
DC. The transducer is designed with a 1/4” flare fitting for
connection to a standard access fitting. If the fitting is con-
figured with a Schrader valve, installation of a shut-off
valve is not required. If the access fitting is not configured
with a Schrader valve, install a shut-off valve between the
transducer and the system. The standard pressure transduc-
er is not compatible with ammonia however, the standard
pressure transducer may be subjected to a vacuum without
damage.
Standard pressure transducers should be mounted in a
vertical position (pressure port down) above crank case
oil level to prevent accumulation of oil in the transducer
port.
Part Number
800-0105 800-0205 800-0505
Pressure Range
0-100
PSIG
0-200
PSIG
0-500
PSIG
Max Overload
PSIG (w/o Dam-
aging xducer)
200 PSIG 400 PSIG 750 PSIG
Max Overload
PSIG (w/o Burst-
ing)
1000 PSI 2000 PSI 2500 PSI
Supply Voltage
12 VDC
Full Scale Out-
put
5±0.1 V DC @ 25° C (1-6 V)
Excitation
<500 PSI 9 to 24 V DC @ 15 mA
nominal; 500 PSI 9 to 24 V DC @ 20
mA nominal
Accuracy
±1% F.S.O. from best fit straight line
including effects of non-linearity,
hysteresis and non-repeatability
Operating Tem-
perature Range
-40° to 105° C (-40° to 221° F)
Hirschmann -40° to 90° C (-40° to
194° F)
EMI Error
Typically less than 1% full scale out-
put error over the frequency range
from 20 mHz to 1 gHz at field
strengths up to 10 volts/meter
Table 10-CPC Standard Pressure Transducer Specifications