Table 6-15 Reactive Power Control (IEEE-1547/ Rule21 and ISO-NE)
Only for CPS SCA50/60KTL-DO/US-480
Grid Reactive Power
Derating
Setting Range
Parameter
Name
Description
IEEE1547
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Default
Max
PFCurveP1%
Power of PF(P) Curve
point 1
0
50
110
0
50
110
0
50
110
PFpCurvePF1
PF of PF(P) Curve point
1
-1.0,
- 0.8
1.0
0.8,
1.0
-1.0,
- 0.8
1.0
0.8,
1.0
-1.0,
- 0.8
1.0
0.8,
1.0
PFCurveP2%
Power of PF(P) Curve
point 2
0
100
110
0
100
110
0
100
110
PFpCurvePF2
PF of PF(P) Curve point
2
-1.0,
- 0.8
-0.9
0.8,
1.0
-1.0,
- 0.8
-0.9
0.8,
1.0
-1.0,
- 0.8
-0.9
0.8,
1.0
PFCurveTriVolt
(V)
The trigger voltage of
PF(P)Curve
100
100
110
100
100
110
100
100
110
PFCurveUndoV
olt (V)
PF curve revocation
voltage
90
90
100
90
90
100
90
90
100
Table 6-16 Reactive Power Control (IEEE-1547 and Rule21)
Only for CPS SCA25KTL-DO-US-208
Grid Reactive Power
Derating
Setting Range
Parameter
Name
Description
IEEE1547
Rule21
Min
Default
Max
Min
Default
Max
PFCurveP1%
Power of PF(P) Curve
point 1
0.0
50.0
110.0
0.0
50.0
110.0
PFpCurvePF1
PF of PF(P) Curve point
1
-1.0,
- 0.8
1.000
0.8,
1.0
-1.0,
- 0.8
1.000
0.8,
1.0
PFCurveP2%
Power of PF(P) Curve
point 2
0.0
100.0
110.0
0.0
100.0
110.0