EasyManua.ls Logo

CPS SCA Series - Page 126

Default Icon
164 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
118
Other Parameters
Setting Range
Parameter
Name
Description
IEEE1547
Rule21
ISO-NE
Min
Default
Max
Min
Default
Max
Min
Defaul
t
Max
Mppt3_OptV
olUpLim
OptiVoltMaxMp
pt3
200.0
1000.0
1500.0
200.0
1000.0
1500.0
200.0
1000.0
1500.0
Table 6-20 Other Parameters
Only for CPS SCA25KTL-DO-US-208
Other Parameters
Setting Range
Parameter
Name
Description
IEEE1547
Rule21
Min
Default
Max
Min
Default
Max
PowerOnDelay
(s)
Startup delay time
0
5
1200
0
5
1200
ReactivePower
Step%
Reactive Step
0.01
25.00
100.00
0.01
25.00
100.00
ErrSoftStartP
(%/P)
Power startup step
after Grid Fault
0.01
0.16
100.00
0.01
0.16
100.00
NormSoftStopP
(%/P)
Normal power step
in soft stop
0.01
6.00
100.00
0.01
6.00
100.00
NormSoftStartP
(%/P)
Normal power step
in soft startup
0.01
4.00
100.00
0.01
4.00
100.00
NormalDerating
Step
Power step in
Derarting
0.01
6.00
100.00
0.01
6.00
100.00
PVSlowStartSt
ep%
PVSlowStartStep
0.01
10.00
100.00
0.01
10.00
100.00
PVSlowStartPw
Delta%
The output power
should be slow
increased due to
the change of PV
illumination at the
0.01
5.00
10.00
0.01
5.00
10.00