Two Trigger Zones
- Where options 1-8 represent zones 1-8. A zone defined as two trigger at
this address will only cause an activation if one of the following conditions are met;
a The zone is triggered twice within the two trigger time period as defined by Address P534E,
P535E or P536E
b Any two zones defined as two trigger activate once each within the two trigger time period
as defined by Address P534E, P535E or P536E
c
A zone defined as two trigger is left violated for longer than the two trigger time period as
defined by Address P534E, P535E or P536E
P450E 1-8E
Zone is 24 Hour
- Where options 1-8 represent zones 1-8. 24 hour zones will activate
whether the panel or partition is armed or disarmed. If an entry delay is also assigned to a 24 hr
zone, the alarm will not trigger unless the zone is in alarm longer than the delay time
programmed. (Default none)
P451E 1-8E
Zone is 24 Hour Fire Zone
- Where options 1-8 represent zones 1-8. 24 hour Fire zones will
activate whether the panel or partition is armed or disarmed. If an entry delay is also assigned to
a 24 hr Fire zone, the alarm will not trigger unless the zone is in alarm longer than the delay time
programmed. A Fire Zone will cause the output to pulse to differentiate it from a burglar alarm.
(Default none)
P452E 1-8E
Zone is 24 Hour
Auto-Reset
- Where options 1-8 represent zones 1-8. 24 hour Auto-Reset
zones will activate whether the panel or partition is armed or disarmed. If an entry delay is also
assigned to a 24 hr Auto-Reset zone, the alarm will not trigger unless the zone is in alarm longer
than the delay time programmed. An Auto-reset zone will seal automatically when the zone input
is restored back to normal i.e. does not require a code to reset an alarm. (Default none)
P453E 1-8E Day Zones - Where options 1-8 represent zones 1-8. Day zones are active during periods
where the panel or partitions are disarmed and revert to normal zones during armed periods
(Default none)
P454E 1-8E Continuous Day Zone - Where options 1-8 represent zones 1-8. The zone acts as a day zone
at all times (Armed and Disarmed) and will operate
day alarms but not normal zone alarms (Default
none)
P455E 1-8E Siren Lockout Zones - Where options 1-8 represent
zones 1-8. Zones with siren lockout designation will
only cause their assigned outputs to operate once
per armed period. Led on = zone locked out. (Default
none)
P456E 1-8E Access Control door position input - Where options 1-8 represent zones 1-8. The door
position input becomes a 24 hour alarm zone and will alarm if the “Control” door is forced open
or left open too long. It will also automatically re-lock the door after the “Control” operation has
occurred and the door has been opened then closed again. (Default none)
P457E 1-8E Access Control Request to exit input - Where options 1-8 represent zones 1-8. The Request
to Exit input will operate the “Control” door output to release the door and start the Door open
Too long Timer. (Default none)
P458E 1-8E Zone will report multiple activations to communicator - Default 1-8. If this option is turned
off then the relevant zone will only report one alarm to a monitoring company during any single
armed period. If it is turned on, the zone can send multiple reports if activated more than once
during a single armed period.
P459E 1-8E Zone will be Monitored for Inactivity - Default none.
A Zone with this option turned on will be checked to
ensure that it is triggered on a regular basis. If the zone
is not triggered within the time period set at P469E then
an alarm will be generated as the detector may have
become faulty or could be masked.
The timer period
as set at address P569E is only active during the disarmed
period. If the timer has started due to inactivity of a zone
input, the elapsed time is remembered at the time of arming and will resume when the alarm is
disarmed.
P460E 1-8E
Cannot Arm if Zone is Unsealed
- Default None. If a zone is unsealed (Not Ready) at the time
of arming, by default the panel will Arm and the zone will either automatically be bypassed or
cause an alarm at the end of the exit delay. If the option is turned on at this address then an
unsealed condition will inhibit the panel from arming until the zone is sealed.
Ignore seal state
Zone is in Area A
1 2 3 4 5 6 7 8
- - - - - - - -