conditions are displayed and reported by the control panel.
Option 7 Cannot arm if the system battery is low. - If this option is turned on, the panel cannot be armed if
the panel battery is low. When the battery is fully charged the panel can then be armed. If this option
is turned off the panel can be armed during these fault conditions.
Option 8 Installer Lockout - Normally if the panel is powered up with the panel tamper open (ie system
tamper alarm active) and in the Disarm state, then the panel will go into installer program mode when
the <PROGRAM> then <ENTER> buttons are pressed. If this option is on, the panel will not allow
access to program mode on power-up and the only valid method of accessing program mode is via
the installer code.
INSTALLER OPTIONS
INSTALLER OPTIONS - P25E 11E
Option 1 - Installer MUST enter program mode via Client mode to reset confirmed alarms
Option 2 - Installer MUST enter program mode via Client mode to reset tamper alarms
Option 3 - Installer MUST enter program mode via Client mode to reset low battery alarms
Option 4 - Installer MUST enter program mode via Client mode to reset supervisory alarms
Option 5 - Cannot Arm if there is a keypad Fault
Option 6 - Cannot Arm if there is a Telephone Line Failure or Comms Fault
Option 7 - 10 Incorrect Code Attempts locks out the keypad for 90 Seconds
Option 8 - User Codes Must be 4-6 digits long
Option 1 Installer MUST enter program mode via Client mode to reset confirmed alarms - If this option is
turned on and a Confirmed alarm has occurred, the alarm cannot be re-armed until the Installer has
reset the alarm. The Installer must access Installer Program Mode via Client Mode to reset the
system. The zones that caused the alarm will latch on (even when disarmed) until reset by the
installer to indicate that lockout is in effect.
Option 2 Installer MUST enter program mode via Client mode to reset tamper alarms - If this option is
turned on and a Tamper alarm has occurred (system or zone tampers), the alarm cannot be re-
armed until the Installer has reset the alarm. The Installer must access Installer Program Mode via
Client Mode to reset the system. The Trouble indication will latch on (even if the tamper alarm has
been cleared) until reset by the installer to indicate that lockout is in effect.
Option 3 Installer MUST enter program mode via Client mode to reset low battery alarms - If this option
is turned on and a Low Battery alarm has occurred, the Installer must access Installer Program Mode
via Client Mode to reset the battery low signal. If option 7 is turned on at location P25E10E the alarm
cannot be re-armed until the Installer has reset the battery low signal.
Option 4 Installer MUST enter program mode via Client mode to reset supervisory alarms - If this option
is turned on and a Detector Supervisory alarm has occurred, the alarm cannot be re-armed until the
Installer has reset the alarm. The Installer must access Installer Program Mode via Client Mode to
reset the supervisory alarm.
Option 5 Cannot Arm if there is a keypad Fault - If this option is turned on and a missing keypad alarm is
present the panel cannot be armed until the keypad has been re-instated.
Option 6 Cannot Arm if there is a Telephone Line Failure or Comms Fault - If this option is turned on and
the control panel has detected a telephone line fault or the dialler failed to get kissed off (Comms
Fault) following an alarm report the panel cannot be armed. To reset the line failure the telephone
line must be re-instated to allow arming again. To reset the Comms Fault alarm, a user must access
the memory.
Option 7 10 Incorrect Code Attempts locks out the keypad for 90 Seconds - If this option is turned off the
panel will create a keypad tamper alarm if more than 4 incorrect codes are entered at a keypad but
the keypad will not be locked out. If this option is turned on the panel will create a keypad tamper
alarm if more than 10 incorrect codes are entered at a keypad and that keypad will then be locked
out for 90 seconds.
Option 8 User Codes Must be 4-6 Digits - If this option is turned on, all User Codes must be between 4-6
digits long. If it is turned off, the User Codes can be 1-6 digits long.