Functions
77
6
Functions
Functions
Function Description
6
Protection
control
High pressure
protection function
When high pressure shows an abnormal rise, used to stop only the
compressor due to malfunction.
Stop due to detection by the thermistor of condenser (subject to all
applicable models)
Actuating temperature: 62 or more
Stop due to detection by the high-pressure switch (only on "-C" models)
Operating pressure: 4.1MPa
Inverter protection
function
AKZ14A–43A-500: When the temperature output of the inverter IPM is
detected to be abnormal, only the compressor is stopped.
Operating temperature: 114
AKZ90A, AKZ56A-500, AKZ90A-500: When the temperature of the inverter
radiator fin is detected to be abnormal, only the compressor is stopped.
Operating temperature: 101.4 (AKZ90A)
93.8 (AKZ56A-500)
87.9 (AKZ90A-500)
* For models AKZ14A–56A, the IPM itself detects the temperature and if
there is an abnormality, only the compressor is stopped.