List of Alarms/Warnings
When an alarm or warning occurs while in operation, the equipment will stop operation in progress and the status
will be displayed as shown below.
1. In order to protect functional parts, the compressor, oil pump, fan, or else stops.
2. In order to alert the customer of the alarm or warning, it is displayed by code or lamp.
In case of alarm
Alarm level
Running/stop Notification
Object
Compressor/heater
Oil pump Fan Restoration Display
Alarm lamp
Level 1 Stop Stop Stop Manual
Alarm code
display
Flash
Alarm code (A6 to UJ)
For details, see P.84 and
85
Lev
el 2 Stop Running Running Manual ON
Stop Running Running Automatic No display OFF
Low room temperature
protection (*1)
Low oil temperature
protection (*2)
*1: Actuates when the room thermistor detects a temperature of -2 or lower.
*2: Actuates when the inlet oil thermistor detects a temperature of 2 or lower.
In case of warning
Warning
level
Running/stop Notification
Object
Compressor Oil pump Fan Restoration Display
Warning lamp
Level 2
Stop Running Running Automatic
Temperature
warning display
(1E to 5E)
ON
Temperature warning
display (1E to 5E)
For details, see P.69–71
Running Running Running
Lev
el 1*
Running Running Running
Warning
code display
Flash
Warning code (A5 to F6)
For details, see P.111
Level 2 ON
No display
(history only)
OFF
*Warning at level 1 will be alarm after cumulative running time has reached 150 hours.