Troubleshooting
5
Troubleshooting
Diagnosis Countermeasures
Control panel display
E5
Malfunction due to Discharge Pipe Temperature or
Overheated Compressor
Is the refrigerant
leaking?
NO
After repairing the leak,
refill the refrigerant.
YES
From the previous page
A
Replace the control
board (A1P).
(See page 122/137)
YES
Replace the
compressor (M2C).
(See page 132/148)
NO
Are insulation
and coil resistance of the
compressor normal?
"Check 3"
(See page 117)