Outdoor Unit - RK(X)S25/35F2V1B SiBE06-708_A
165 Removal Procedure
7
Release the discharge
pipe thermistor.
Be careful not to lose the clip
for the thermistor.
8
Cut the clamp.
9
Pull out the outdoor
heat exchanger
thermistor.
Be careful not to lose the clip
for the thermistor.
Step
Procedure Points
(R0267)
Discharge pipe thermistor
(R12279)
Clip
(R7221)
(R7222)
Outdoor heat exchanger
thermistor
Clip