EasyManuals Logo

Daikin Floor Standing Type F-Series User Manual

Daikin Floor Standing Type F-Series
283 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
Problem Symptoms and Measures SiBE06-708_A
79 Service Diagnosis
2. Problem Symptoms and Measures
Symptom Check Item Details of Measure Reference
Page
The units does not operate. Check the power supply. Check to make sure that the rated voltage is
supplied.
Check the type of the indoor units. Check to make sure that the indoor unit type is
compatible with the outdoor unit.
Check the outdoor temperature. Heating operation cannot be used when the
outdoor temperature is 20°C or higher, and
cooling operation cannot be used when the
outdoor temperature is below –10°C.
Diagnose with remote controller
indication.
—83
Check the remote controller
addresses.
Check to make sure that address settings for
the remote controller and indoor unit are
correct.
Operation sometimes
stops.
Check the power supply. A power failure of 2 to 10 cycles stops air
conditioner operation. (Operation lamp OFF)
Check the outdoor temperature. Heating operation cannot be used when the
outdoor temperature is 20°C or higher, and
cooling operation cannot be used when the
outdoor temperature is below –10°C.
Diagnose with remote controller
indication.
—83
The unit operates but does
not cool, or does not heat.
Check for wiring and piping errors in
the connection between the indoor
and outdoor units.
Conduct the wiring/piping error check described
on the product diagnosis label.
Check for thermistor detection errors. Check to make sure that the thermistor is
mounted securely.
Check for faulty operation of the
electronic expansion valve.
Set the units to cooling operation, and check
the temperature of the liquid pipe to see if the
electronic expansion valve works.
Diagnose with remote controller
indication.
—83
Diagnose by service port pressure
and operating current.
Check for refrigerant shortage. 121
Large operating noise and
vibrations
Check the output voltage of the
power module.
—132
Check the power module.
Check the installation condition. Check to make sure that the required spaces
for installation (specified in the installation
manual, etc.) are provided.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Floor Standing Type F-Series and is the answer not in the manual?

Daikin Floor Standing Type F-Series Specifications

General IconGeneral
BrandDaikin
ModelFloor Standing Type F-Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals