SiBE06-708_A Control Specification
Function and Control 52
3.10 Defrost Control
Outline Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than a certain value to finish.
Detail Conditions for Starting Defrost
The starting conditions is determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than minutes of accumulated time pass since the start of the operation, or ending
the previous defrosting.
Conditions for Canceling Defrost
The judgment is made with outdoor heat exchanger temperature. ( °C)
RK(X)S25/35F2V1B
RK(X)S25/35G2V1B
RK(X)S25/35G2V1B9
RK(X)S50F2V1B
RK(X)S50G2V1B
(minutes) 28 28 44
(Hz) 76 76 55
(Hz) 86 86 90
(seconds) 50 50 60
(seconds) 60 60 120
(seconds) 600 600 460
(seconds) 50 60 30
(pulse) 450 450 450
(pulse) 350 350 450
(pulse) 450 450 450
(°C) 4 ~ 22 4 ~ 18 4 ~ 12
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0Hz
Hz
Hz
5 sec.
pulse
pulsepulse
Initial opening
PI control
5 sec.
sec.
(R12211)
Electronic expansion
valve opening
sec.
sec.
sec.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Floor Standing Type F-Series and is the answer not in the manual?

Daikin Floor Standing Type F-Series Specifications

General IconGeneral
BrandDaikin
ModelFloor Standing Type F-Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals