Main Functions SiBE06-708_A
35 Function and Control
1.5 Program Dry Operation
Outline Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
Detail The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates in the dry mode with an appropriate capacity for each zone to
maintain the temperature and humidity at a comfortable level.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24ºC or more
Room thermistor
temperature at start-up
X
2.5ºC
X
0.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
23.5ºC
X
2.0ºC
X
0.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
~
18ºC
18ºC X
2.0ºC
X
0.5ºC = 17.5ºC
or
Y + 0.5ºC (zone B)
continues for 10 min.
17.5ºC
~
Z
X
Y
Zone B
Zone B
Zone A = Thermostat OFF
Zone C = Thermostat ON
+0.5ºC
(R11581)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Floor Standing Type F-Series and is the answer not in the manual?

Daikin Floor Standing Type F-Series Specifications

General IconGeneral
BrandDaikin
ModelFloor Standing Type F-Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals