SiBE06-708_A Outdoor Unit - RK(X)S25/35G2V1B
Removal Procedure 190
3.3 Removal of Thermistors
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure Points
1
Release the discharge
pipe thermistor.
Be careful not to lose the clip
for the thermistor.
2
Cut the clamp.
3
Pull out the outdoor
heat exchanger
thermistor.
Be careful not to lose the clip
for the thermistor.
(R0267)
Discharge pipe thermistor
(R12279)
Clip
(R7221)
(R7222)
Outdoor heat exchanger
thermistor
Clip