EasyManuals Logo

Daikin Floor Standing Type F-Series User Manual

Daikin Floor Standing Type F-Series
283 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #242 background imageLoading...
Page #242 background image
Outdoor Unit - RK(X)S25/35G2V1B9 SiBE06-708_A
231 Removal Procedure
Step
Procedure Points
3
Heat up the brazed part
of the suction side and
disconnect.
Note:
Do not use a metal saw for
cutting pipes by all means
because the sawdust comes
into the circuit.
When withdrawing the pipes,
be careful not to pinch them
firmly with pliers. The pipes
may get deformed.
Provide a protective sheet or
a steel plate so that the
brazing flame cannot
influence peripheries.
Be careful so as not to burn
the compressor terminals,
the name plate, the heat
exchanger fin.
4
Lift the compressor up
and remove it.
(R12032)
Suction side
(R7254)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Floor Standing Type F-Series and is the answer not in the manual?

Daikin Floor Standing Type F-Series Specifications

General IconGeneral
BrandDaikin
ModelFloor Standing Type F-Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals