Group 22: Accel/Decel
This group denes ramps that control the rate of acceleration and deceleration. You dene these ramps as a pair, one for
acceleration and one for deceleration. You can dene two pairs of ramps and use a digital input to select one or the other pair.
Table 14: Group 22: Accel/Decel
Code Description Range Resolution Default S
2202 ACCELER TIME 1
0.0…
1800.0 s
0.1 s 30.0 s
Sets the acceleration time for zero to maximum frequency for ramp pair 1. See A in the gure.
Actual acceleration time also depends on 2204 RAMP SHAPE 1.
• See 2008 MAXIMUM FREQ, page 28.
2203 DECELER TIME 1
0.0…
1800.0 s
0.1 s 30.0 s
Sets the deceleration time for maximum frequency to zero for ramp pair 1.
Actual deceleration time also depends on 2204 RAMP SHAPE 1.
• See 2008 MAXIMUM FREQ, page 28.