Code Description Range Resolution Default S
2605 U/f RATIO 1, 2 1 2 (SQUARED)
Selects the form for the U/f (voltage to frequency) ratio below eld weakening point.
1 = LINEAR – Preferred for constant torque applications.
2 = SQUARED – Preferred for centrifugal pump and fan applications. (SQUARED is more silent for most operating frequencies.)