EasyManua.ls Logo

Daikin MD5 - Serial Communications

Daikin MD5
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 62: Drive Control Terminal Descriptions
X1 Drive Control Terminal Description
Analog I/O
1 SCR Terminal for signal cable screen. (Connected internally to chassis ground.)
2 AI1
Analog input channel 1, programmable. Default
2
= external reference. Resolution 0.1%, accuracy ±1%.
J1:AI1 OFF: 0(2)…10 V (Ri = 312 kΩ) or, for OFF for ON
J1:AI1 ON: 0(4)…20 mA (Ri = 100 Ω)
3 AGND Analog input circuit common (connected internally to chassis gnd. through 1 MΩ).
4 +10 V Potentiometer reference source: 10 V ±2%, max. 10 mA (1kΩ < R < 10kΩ).
5 AI2
Analog input channel 2, programmable. Default
2
= PID feedback. Resolution 0.1%, accuracy ±1%.
J1:AI2 OFF: 0(2)…10 V (Ri = 312 kΩ) or, for OFF for ON
J1:AI2 ON: 0(4)…20 mA (Ri = 100 Ω)
6 AGND Analog input circuit common (connected internally to chassis gnd. through 1 MΩ).
7 AO1
Analog output, programmable. Default
2
= frequency. 0…20 mA (load < 500 Ω).
8 AO2
Analog output, programmable. Default
2
= current. 0…20 mA (load < 500 Ω).
9 AGND Analog output circuit common (connected internally to chassis gnd. through 1 MΩ).
Digital Inputs
1
10 +24V. Auxiliary voltage output 24 VDC / 250 mA (reference to GND), short circuit protected
11 GND Auxiliary voltage output common (connected internally as oating).
12 DCOM
Digital input common. To activate a digital input, there must be ≥+10 V (or ≤-10 V) between that input and DCOM. The 24 V may be
provided by the MD5 (X1-10) or by an external 12…24 V source of either polarity.
13 DI1 Digital input 1, programmable. Default
2
= start/stop.
14 DI2 Digital input 2, programmable. Default
2
= not congured.
15 DI3
Digital input 3, programmable. Default
2
= constant (preset) speed.
16 DI4 Digital input 4, programmable. Default
2
= safety interlock.
17 DI5 Digital input 5, programmable. Default
2
= not congured.
18 DI6
Digital input 6, programmable. Default
2
= not congured.
Relay Outputs
19 RO1C Relay output 1, programmable. Default
2
= Ready
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)
20 RO1A
21 RO1B
22 RO2C
Relay output 2, programmable. Default2 = Running
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)
23 RO2A
24 RO2B
25 RO3C
Relay output 3, programmable. Default2 = Fault (-1)
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)
26 RO3A
27 RO3B
1 Digital input impedance 1.5 kΩ. Maximum voltage for digital inputs is 30 V.
2 Default values depend on the macro used. Values specied are for the HVAC default macro. See Application Macros on page 9
.
You can wire the digital input terminals in either a PNP or NPN
conguration.
Serial Communications
Terminals 28…32 provide RS485 serial communication
connections used to control or monitor the drive from a eldbus
controller. See Embedded Fieldbus on page 45 for details.
OM 1191 • MD5 VFD 86 www.DaikinApplied.com
TeChniCal daTa

Table of Contents

Related product manuals