Group 30: Fault Functions
This group denes situations that the drive should recognize as potential faults and denes how the drive should respond if the
fault is detected.
Table 16: Group 30: Fault Functions
Code Description Range Resolution Default S
3003 EXTERNAL FAULT 1 -6…6 1
0 (NOT
SEL)
Denes the External Fault 1 signal input and the drive response to an external fault.
0 = NOT SEL – External fault signal is not used.
1 = DI1 – Denes digital input DI1 as the external fault input.
Activating the digital input indicates a fault. The drive displays a fault (14, EXT FAULT 1) and the drive coasts to stop.
2…6 = DI2…DI6 – Denes digital input DI2…DI6 as the external fault input.
• See DI1 above.
-1 = DI1(INV) – Denes an inverted digital input DI1 as the external fault input.
• De-activating the digital input indicates a fault. The drive displays a fault (14, EXT FAULT 1) and the drive coasts to stop.
-2…-6 = DI2(INV)…DI6(INV) – Denes an inverted digital input DI2…DI6 as the external fault input.
• See DI1(INV) above.
OM 1191 • MD5 VFD 32 www.DaikinApplied.com