Group 98: Options
This group congures for options, in particular, enabling serial communication with the drive.
Table 23: Group 98: Options
Code Description Range Resolution Default S
9802 COMM PROT SEL 0…5 1
0 (NOT
SEL)
Selects the communication protocol.
0 = NOT SEL – No communication protocol selected.
1 = STD MODBUS – The drive communicates with Modbus via the RS485 channel (X1-communications, terminal).
• See also Group 53: EFB PROTOCOL.
2 = N2 – Enables eldbus communication with the drive using Metasys N2 protocol via the RS485 serial link (X1-communications terminal).
3 = FLN – Enables eldbus communication with the drive using FLN protocol via the RS485 serial link (X1-communications terminal).
4 = EXT FBA – The drive communicates via a eldbus adapter module in option slot 2 of the drive.
5 = BACNET – Enables eldbus communication with the drive using BACnet protocol via the RS485 serial link (X1-communications terminal).
OM 1191 • MD5 VFD 44 www.DaikinApplied.com