Relay Output Control
Using the eldbus for relay output control requires:
Drive parameter values set as dened below.
Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is dened by the
Protocol Reference, which is protocol dependent.)
For example: To control relays 1 and 2 using serial
communication:
Set parameters 1401 RELAY OUTPUT 1 and 1402 RELAY
OUTPUT 1 = 35 (COMM).
Then, for example using N2:
To turn Relay 1 On: Force object B07 to On.
To turn Relay 2 On: Force object B08 to On.
To turn both Relay 1 and 2 On: Force objects B07 and
B08 On.
NOTE: Relay status feedback occurs without conguration
as dened below.
Table 29: Relay Output Control Parameters
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN BACnet
Daikin DRV DCU PROFILE
1401
RELAY
OUTPUT 1
35 (COMM)
Relay Output
1 controlled by
eldbus.
40134 bit 0 or 00033 BO7 40 BO0
1402
RELAY
OUTPUT 2
35 (COMM)
Relay Output
2 controlled by
eldbus.
40134 bit 1 or 00034 BO8 41 BO1
1403
RELAY
OUTPUT 3
35 (COMM)
Relay Output
3 controlled by
eldbus.
40134 bit 2 or 00035 BO9 42 BO2
1410
1
RELAY
OUTPUT 4
35 (COMM)
Relay Output
4 controlled by
eldbus.
40134 bit 3 or 00036 BO10 43 BO3
1411
1
RELAY
OUTPUT 5
35 (COMM)
Relay Output
5 controlled by
eldbus.
40134 bit 4 or 00037 BO11 44 BO4
1412
1
RELAY
OUTPUT 6
35 (COMM)
Relay Output
6 controlled by
eldbus.
40134 bit 5 or 00038 BO12 45 BO5
0122 RO 1-3 STATUS
Relay 1…3
status.
40122 0122 BI4… BI6 76… 78 BI0… BI2
0123 RO 4-6 STATUS
Relay 4…6
status.
40123 0123 BI7… BI9 79… 81 BI3… BI5
1. More than 3 relays requires the addition of a relay extension module.
OM 1191 • MD5 VFD 52 www.DaikinApplied.com