Miscellaneous Drive Control
Using the eldbus for miscellaneous drive control requires:
Drive parameter values set as dened below.
Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is dened by the
Protocol Reference, which is protocol dependent.)
Table 28: Miscellaneous Drive Control Parameters
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN BACnet
Daikin DRV DCU PROFILE
1601 RUN ENABLE
7 (COMM) (Not
Recommended)
Run enable by
eldbus.
40001 bit 3
40031 bit 6
(inverted)
BO4 35 BV12
1604
FAULT RESET
SEL
8 (COMM)
Fault reset by
eldbus.
40001 bit 7 40031 bit 4 BO6 94 BV14
1606 LOCAL LOCK 8 (COMM)
Source for local
lock selection is
the eldbus.
Does not apply 40031 bit 14
1607 PARAM SAVE 1 (SAVE)
Saves altered
parameters to
memory (then
value returns
to 0).
41607 40032 bit 2 BO18 N/A
1
1608 START ENABLE 1
7 (COMM) (Not
Recommended)
Source for
start enable 1
is the eldbus
Command word.
Does not apply.
40032 bit 2 BV20
1609 START ENABLE 2
7 (COMM) (Not
Recommended)
Source for
start enable 2
is the eldbus
Command word.
40032 bit 3 BV21
2013 MIN TORQUE SEL 7 (COMM)
Source for
minimum torque
selection is the
eldbus.
40031 bit 15
2014
MAX TORQUE
SEL
7 (COMM)
Source for
maximum torque
selection is the
eldbus.
2201 ACC/DEC 1/2 SEL 7 (COMM)
Source for ramp
pair selection is
the eldbus.
40031 bit 10
1. Use Memorize Point command.
eMbedded fieldbUs
www.DaikinApplied.com 51 OM 1191 • MD5 VFD