Duplicate Stations
If two or more stations have duplicate numbers:
Two or more drives cannot be addressed.
Every time there is a read or write to one particular
station, the value for 5307 EFB CRC ERRORS or 5308
EFB UART ERRORS advances.
To correct: Check all station numbers and edit conicting
values.
Swapped Wires
If the communication wires are swapped (terminal A on one
drive is connected to terminal B on another):
The value of 5306 EFB OK MESSAGES does not
advance.
The values of 5307 EFB CRC ERRORS and 5308 EFB
UART ERRORS are advancing.
To correct: Check that the EIA-485 lines are not swapped.
Fault 28 – Serial 1 Err
If the drive’s control panel shows fault code 28 “SERIAL 1
ERR”, check for either of the following:
The master system is down. To correct, resolve problem
with master system.
The communication connection is bad. To correct, check
communication connection at the drive.
The time-out selection for the drive is too short for the
given installation. The master is not polling the drive
within the specied time-out delay. To correct, increase
the time set by parameter 3019 COMM FAULT TIME.
Fault 31 – EFB1
For BACnet: If the drive’s control panel shows fault code 31
“EFB1”, the drive has an invalid Device Object Instance ID. To
correct, use parameters 5311 and 5317 and establish a unique
drive ID that is in the range 1 to 4,194,303.
Faults 31…33 – EFB1…EFB3
Except as noted above, these three EFB fault codes (listed for
the drive in Diagnostics on page 74, fault codes 31…33) are
not used.
Intermittent off-line occurrences
The problems described above are the most common
problems encountered with MD5 serial communication.
Intermittent problems might also be caused by:
Marginally loose connections,
Wear on wires caused by equipment vibrations,
Insufcient grounding and shielding on both the devices
and on the communication cables.
Two conductor wire (plus shield) is in use instead of the
recommended three conductor wire (plus shield), see
page 46.
eMbedded fieldbUs
www.DaikinApplied.com 57 OM 1191 • MD5 VFD