For basic serial communication set-up, perform the
following steps:
1. Connect RS485 serial communication wiring to
terminals (+)68 and (-)69.
1a Use shielded serial communication cable
(recommended).
1b See chapter 5.6 Connecting to Ground for
proper grounding.
2. Select the following parameter settings:
2a Protocol type in parameter 8-30 Protocol.
2b Drive address in parameter 8-31 Address.
2c Baud rate in parameter 8-32 Baud Rate.
61
68
69
+
130BB489.10
RS485
Illustration 5.21 Serial Communication Wiring Diagram
5.8.6 Wiring Safe Torque O (STO)
The Safe Torque O (STO) function is a component in a
safety control system. STO prevents the unit from
generating the voltage required to rotate the motor.
To run STO, more wiring for the drive is required. Refer to
Safe Torque O Operating Guide for further information.
5.8.7 Wiring the Space Heater
The space heater is an option used to prevent conden-
sation from forming inside the enclosure when the unit is
turned o. It is designed to be eld wired and controlled
by an HVAC management system.
Specications
Nominal voltage: 100–240
Wire size: 12–24 AWG
5.8.8 Wiring the Auxiliary Contacts to the
Disconnect
The disconnect is an option that is installed at the factory.
The auxiliary contacts, which are signal accessories used
with the disconnect, are not installed at the factory to
allow more exibility during installation. The contacts snap
into place without the need for tools.
Contacts must be installed in
specic locations on the
disconnect depending upon their functions. Refer to the
datasheet included in the accessory bag that comes with
the drive.
Specications
U
i
/[V]: 690
U
imp
/[kV]: 4
Pollution degree: 3
I
th
/[A]: 16
Cable size: 1...2x0.75...2.5 mm
2
Maximum fuse: 16 A/gG
NEMA: A600, R300, wire size: 18–14 AWG, 1(2)
5.8.9 Wiring the Brake Resistor Temperature
Switch
The brake resistor terminal block is located on the power
card and allows for the connection of an external brake
resistor temperature switch. The switch can be congured
as normally closed or normally open. If the input changes,
a signal trips the drive and shows alarm 27, Brake chopper
fault on the LCP display. At the same time, the drive stops
braking and the motor coasts.
1. Locate the brake resistor terminal block (terminals
104–106) on the power card. See Illustration 3.3.
2. Remove the M3 screws that hold the jumper to
the power card.
3. Remove the jumper and wire the brake resistor
temperature switch in 1 of the following congu-
rations:
3a Normally closed. Connect to terminals
104 and 106.
3b Normally open. Connect to terminals
104 and 105.
4. Secure the switch wires with the M3 screws.
Torque to 0.5-0.6 Nm (5 in lb).
Electrical Installation VLT® HVAC Drive FC 102
44 Danfoss A/S © 01/2017 All rights reserved. MG16O102
55

Table of Contents

Other manuals for Danfoss FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 102 and is the answer not in the manual?

Danfoss FC 102 Specifications

General IconGeneral
BrandDanfoss
ModelFC 102
CategoryDC Drives
LanguageEnglish

Related product manuals