FC 300 Operating Instructions
How to Install
380-500 V, 525-600 V
FC 30X Bussmann Bussmann Bussmann SIBA Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
kW Type RK1 Type J Type T Type RK1 Type RK1 Type CC Type RK1
K37-1K5 KTS-R10 JKS-10 JJS-10 5017906-010 KLS-R10 ATM-R10 A6K-10R
2K2-4K0 KTS-R20 JKS-20 JJS-20 5017906-020 KLS-R20 ATM-R20 A6K-20R
5K5-7K5 KTS-R30 JKS-30 JJS-30 5012406-032 KLS-R30 ATM-R30 A6K-30R
11K KTS-R40 JKS-40 JJS-40 5014006-040 KLS-R40 A6K-40R
15K KTS-R50 JKS-50 JJS-50 5014006-050 KLS-R50 A6K-50R
18K KTS-R60 JKS-60 JJS-60 5014006-063 KLS-R60 A6K-60R
22K KTS-R80 JKS-80 JJS-80 5014006-100 KLS-R80 A6K-80R
KTS-fuses from Bussmann may sub stitute KTN for 240 V frequency converters.
FWH-fuses from Bussmann may substitute FWX for 240 V frequency converters.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V fre quency converters.
L50S fuses from LITTEL FUSE may substitute L5 0S fuses for 240 V frequency converters.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V frequency converters.
A50X fuses from FERRAZ SHAWMUT may substitute A 25X for 240 V frequency converters.
23
MG.33.A7.02 - VLT is a registered Danfoss trademark