EasyManua.ls Logo

Danfoss FC 300

Danfoss FC 300
234 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
If S-ramps are selected then set the level of non-linear jerk compensation required. Set jerk com-
pensation by defining the proportion of ramp-up and ramp-down times where acceleration and
deceleration are variable (i.e. increasing or decreasing). The S-ramp acceleration and deceleration
settings are defined as a percentage of the actual ramp time.
3-40 Ramp 1 Type
Option: Function:
Select the ramp type, depending on requirements for accelera-
tion/deceleration.
A linear ramp will give constant acceleration during ramping. An
S-ramp will give non-linear acceleration, compensating for jerk
in the application.
[0]
*
Linear
[1] S-ramp Const Jerk Acceleration with lowest possible jerk.
[2] S-ramp Const Time S-ramp based on the values set in par. 3-41 and 3-42.
NB!
If S-ramp [1] is selected and the reference during ramping is changed the ramp time
may be prolonged in order to realize a jerk free movement which may result in a
longer start or stop time.
Additional adjustment of the S-ramp ratios or switching initiators may be necessary.
3-41 Ramp 1 Ramp up Time
Range: Function:
Size re-
lated
[0.01 - 3600.00 s] Enter the ramp-up time, i.e. the acceleration time from 0 RPM
to the rated motor speed n
M,N
(par. 1-25). Choose a ramp-up
time such that the output current does not exceed the current
limit in par. 4-18 during ramping. The value 0.00 corresponds
to 0.01 sec. in speed mode. See ramp-down time in par. 3-42.
Par
.3 41 =
t
acc
s xn
M
,
N
(
par
.1 25
)
RPM
Δ
ref RPM
FC 300 Programming Guide 2. How to Programme
MG.33.M2.02 - VLT
®
is a registered Danfoss trademark
77
2

Other manuals for Danfoss FC 300

Related product manuals