8-05 End-of-Timeout Function
Option: Function:
•
[7] Set-up 1.
•
[8] Set-up 2.
•
[9] Set-up 3.
•
[10] Set-up 4.
[0] Hold set-
up
Retains the set-up selected in
parameter 8-04 Control Timeout Function and
displays a warning, until parameter 8-06 Reset
Control Timeout toggles. Then the frequency
converter resumes its original set-up.
[1] * Resume
set-up
Resumes the set-up active before the time-out.
8-06 Reset Control Timeout
Option: Function:
This parameter is active only when option [0] Hold
set-up has been selected in parameter 8-05 End-of-
Timeout Function.
[0] * Do not
reset
Retains the set-up specied in
parameter 8-04 Control Timeout Function:
•
[7] Set-up 1
•
[8] Set-up 2
•
[9] Set-up 3
•
[10] Set-up 4
[1] Do
reset
Returns the frequency converter to the original
set-up following a control word timeout. When the
value is set to [1] Do reset, the frequency converter
performs the reset and immediately reverts to the
[0] Do not reset setting.
8-07 Diagnosis Trigger
Option: Function:
Select [0] Disable to send no extended
diagnosis data (EDD). Select [1] Trigger on
alarms to send EDD upon alarms or [2] Trigger
alarm/warn. to send EDD upon alarms, or
warnings. Not all eldbusses support the
diagnosis functions. This parameter has no
function for BACnet.
[0] * Disable
[1] Trigger on
alarms
[2] Trigger
alarm/warn.
8-08 Readout Filtering
If the speed feedback value readouts on eldbus are uctuating,
this function is used. Select ltered, if the function is required. A
power cycle is required for changes to take eect.
Option: Function:
[0] Motor Data Std-
Filt.
Normal bus readouts.
[1] Motor Data LP-
Filter
Filtered bus readouts of the
following parameters:
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage
16-14 Motor current
16-16 Torque [Nm]
16-17 Speed [RPM]
16-22 Torque [%]
16-25 Torque [Nm] High
3.9.2 8-1* Ctrl. Word Settings
8-10 Control Prole
Option: Function:
Select the interpretation of the control
and status words corresponding to the
installed eldbus. Only the selections valid
for the eldbus installed in slot A are
visible in the LPC display.
[0] * FC prole
[1] PROFIdrive
prole
[5] ODVA Available only with MCA 104 DeviceNet,
MCA 121 Ethernet/IP.
[7] CANopen DSP
402
8-13 Congurable Status Word STW
Option: Function:
This parameter enables conguration of bits
12–15 in the status word.
[0] No function
[1] * Prole Default Function corresponds to the prole default
selected in parameter 8-10 Control Prole.
[2] Alarm 68
Only
Only set in case of an Alarm 68.
[3] Trip excl.
Alarm 68
Set in case of a trip, except if Alarm 68
executes the trip.
[10] T18 DI status. The bit indicates the status of terminal 18.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[11] T19 DI status. The bit indicates the status of terminal 19.
0 indicates that the terminal is low.
1 indicates that the terminal is high.
[12] T27 DI status. The bit indicates the status of terminal 27.
0 indicates that the terminal is low.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
90 Danfoss A/S © 03/2015 All rights reserved. MG11CE02
33