3.9 Parameters: 8-** Main Menu -
Communications and Options
3.9.1 8-0* General Settings
8-01 Control Site
Option: Function:
The setting in this parameter overrides the
settings in parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select.
[0] Digital and
ctrl.word
Control by using both digital input and
control word.
[1] Digital only Control by using digital inputs only.
[2] Controlword
only
Control by using control word only.
8-02 Control Source
Option: Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the source of the control word: 1 of 2
serial interfaces, or 4 installed options. During
initial power-up, the frequency converter
automatically sets this parameter to [3] Option
A if it detects a valid eldbus option installed
in slot A. If the option is removed, the
frequency converter detects a change in the
conguration, sets parameter 8-02 Control
Source back to default setting [01] FC Port, and
the frequency converter then trips. If an
option is installed after initial power-up, the
setting of parameter 8-02 Control Source does
not change but the frequency converter trips
and displays: Alarm 67, Option Changed.
[0] None
[1] FC Port
[2] USB Port
[3] Option A
[4] Option B
[5] Option C0
[6] Option C1
[30] External Can
8-03 Control Timeout Time
Range: Function:
Size
related*
[0.5 -
18000 s]
Enter the maximum time expected to pass
between the reception of 2 consecutive
telegrams. If this time is exceeded, it
indicates that the serial communication has
stopped. The function selected in
parameter 8-04 Control Timeout Function
Control Time-out Function is then carried out.
8-03 Control Timeout Time
Range: Function:
In BACnet, the control timeout is only
triggered if some specic objects are written.
The object list holds information on the
objects that triggers the control timeout:
Analog outputs
Binary outputs
AV0
AV1
AV2
AV4
BV1
BV2
BV3
BV4
BV5
Multistate outputs
8-04 Control Timeout Function
Option: Function:
Select the timeout function. The
timeout function is activated when the
control word fails to be updated
within the time period specied in
parameter 8-03 Control Timeout Time.
[20] N2 Override Release only appears
after setting the Metasys N2 protocol.
[0] * O
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max. speed
[5] Stop and trip
[7] Select setup 1
[8] Select setup 2
[9] Select setup 3
[10] Select setup 4
[20] N2 Override
Release
[27] Forced stop and
trip
8-05 End-of-Timeout Function
Option: Function:
Select the action after receiving a valid control
word following a time-out. This parameter is
active only when parameter 8-04 Control
Timeout Function is set to
Parameter Descriptions Programming Guide
MG11CE02 Danfoss A/S © 03/2015 All rights reserved. 89
3 3

Table of Contents

Other manuals for Danfoss Metasys N2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Metasys N2 and is the answer not in the manual?

Danfoss Metasys N2 Specifications

General IconGeneral
BrandDanfoss
ModelMetasys N2
CategoryDC Drives
LanguageEnglish

Related product manuals