8-53 Start Select
Option: Function:
[1] Bus Activates a start command via the serial
communication port or eldbus option.
[2] Logic
AND
Activates a start command via the eldbus/serial
communication port, AND additionally via 1 of
the digital inputs.
[3] * Logic OR Activates a start command via the eldbus/serial
communication port, OR via 1 of the digital
inputs.
8-54 Reversing Select
Option: Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the frequency converter reverse
function via the terminals (digital input) and/or via
the eldbus.
[0] Digital
input
Activates reverse command via a digital input.
[1] Bus Activates reverse command via the serial
communication port or eldbus option.
[2] Logic
AND
Activates reverse command via the eldbus/serial
communication port, AND via 1 of the digital
inputs.
[3] Logic OR Activates reverse command via the eldbus/serial
communication port OR via 1 of the digital inputs.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the eldbus.
[0] Digital
input
Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial
communication port, or eldbus option.
[2] Logic
AND
Activates the set-up selection via the eldbus/
serial communication port, AND via 1 of the
digital inputs.
[3] * Logic OR Activates the set-up selection via the eldbus/
serial communication port OR via 1 of the
digital inputs.
8-56 Preset Reference Select
Option: Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
eldbus.
8-56 Preset Reference Select
Option: Function:
[0] Digital
input
Activates preset reference selection via a digital
input.
[1] Bus Activates preset reference selection via the
serial communication port, or eldbus option.
[2] Logic AND Activates preset reference selection via the
eldbus/serial communication port, AND via 1
of the digital inputs.
[3] * Logic OR Activates the preset reference selection via the
eldbus/serial communication port, OR via 1 of
the digital inputs.
3.9.6 8-7* BACnet
NOTICE
Parameters in this group are active only when
parameter 8-30 Protocol is set to [5] BACnet.
8-70 BACnet Device Instance
Range: Function:
1* [0 - 4194302 ] Enter a unique ID number for the BACnet
device.
8-72 MS/TP Max Masters
Range: Function:
127* [1 - 127 ] Dene the address of the master which holds
the highest address in this network. Decreasing
this value optimises polling for the token.
8-73 MS/TP Max Info Frames
Range: Function:
1* [1 - 65534 ] Dene how many info/data frames the device
is allowed to send while holding the token.
8-74 "I-Am" Service
Option: Function:
[0] * Send at power-
up
[1] Continuously Select whether the device should send the
"I-Am" service message only at power-up,
or continuously with an interval of approx-
imately 1 min.
8-75 Initialisation Password
Range: Function:
Size related* [1 - 20 ]