Technical item or
function
Technical item or function Technical information
EMC (at default
settings)
Immunity Fulfils EN 61800-3 (2004), 1st and 2nd environment
Emissions 200–500 V: EN 61800-3 (2004), category C2.
600–690 V: EN 61800-3 (2004), category C3.
All: The product is configurable to category C4 for installation on IT net-
works. The drive can be modified for IT type mains. See 6.6 Installation in
an IT System. The IP00/UL Open Type drive has by default category C4.
Noise level Average noise level (min-max)
sound pressure level in dB(A)
The sound pressure depends on the cooling fan speed, which is controlled
in accordance with the drive temperature.
MR4: 45–56
MR5: 57–65
MR6: 63–72
MR7: 43–73
MR8: 58–73
MR9: 54–75
Safety standards - IEC/EN 61800-5-1, UL 61800-5-1, CSA C22.2 No.274.
Approvals - CE, cULus, RCM, KC, EAC, UA. (See the nameplate of the drive for more ap-
provals.)
The UL approval is valid for input voltage up to 600 V.
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711
140 | Danfoss A/S © 2019.05