Technical item or
function
Technical item or function Technical information
Protections Overvoltage trip limit Mains voltage 240 V: 456 VDC
Mains voltage 500 V: 911 VDC
Mains voltage 600 V: 1094 VDC
Mains voltage 690 V: 1258 VDC
Undervoltage trip limit Depends on mains voltage (0.8775 x mains voltage):
Mains voltage 240 V: trip limit 211 VDC
Mains voltage 400 V: trip limit 351 VDC
Mains voltage 500 V: trip limit 438 VDC
Mains voltage 525 V: trip limit 461 VDC
Mains voltage 600 V: trip limit 527 VDC
Mains voltage 690 V: trip limit 606 VDC
Earth fault protection Yes
Mains supervision Yes
Motor phase supervision Yes
Overcurrent protection Yes
Unit overtemperature protec-
tion
Yes
Motor overload protection
Yes.
(1)
The motor overload protection activates at 110% of the full load cur-
rent.
Motor stall protection Yes
Motor underload protection Yes
Short-circuit protection of +24
V and +10 V reference voltages
Yes
1
For the motor thermal memory and the memory retention function to obey the UL 61800-5-1 requirements, you must use the system software version FW0159V003 or a newer
version. If you use an older system software version, you must install a motor overtemperature protection to obey the UL regulations.
Specifications
Operating Guide | VACON® 100 Wall-mounted Drives
AQ298036140958en-000101 / DPD01711| 141