EasyManuals Logo
Home>Danfoss>DC Drives>VLT 2800

Danfoss VLT 2800 Design Guide

Danfoss VLT 2800
162 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #135 background imageLoading...
Page #135 background image
5.1.20 Generic EMC Standards / Product Standards
Standard/environment Industrial environment Residential, commercial and light industry
EMC Product Standard EN61800-3 EN61800-3
1st edition, 1996 Unrestricted Restricted Unrestricted Restricted
2nd edition, 2004 Category 3 Category 4 Category 1 Category 2
EMC Basic Standard, EN55011, Cable-
borne/Radiated
Class A2
EMC plan
1)
Class B Class A1
Generic EMC standards EN 61000-6-4 EN 61000-6-3
EMC Basis Standard, EN55011, Cable-
borne/Radiated
Class A Class B
1) Described in details in the EMC Product Standard. This category is among other things for complex installations (for instance IT supply
networks).
The following system results are achieved on a system consisting of a VLT
®
2800 frequency converter with screened/
armoured control cable, control box with potentiometer, screened/armoured motor cable and screened/armoured brake
cable as well as an LCP2 with cable.
VLT 2803-2875 Emission
Industrial environment Residential, commercial and light industry
EN 55011 class 1A EN 55011 class 1B
Set-up Cable-borne
150 kHz-30 MHz
Radiated
30 MHz-1 GHz
Cable-borne
150 kHz-30 MHz
Radiated
30 MHz-1 GHz
3x480 V version with 1A RFI
filter
Yes
25 m screened/
armoured
Yes
25 m screened/armoured
No No
3x480 V version with 1A RFI
filter (R5: For IT mains)
Yes
5 m screened/armoured
Yes
5 m screened/armoured
No No
1x200 V version with 1A RFI
filter
1)
Yes
40 m screened/
armoured
Yes
40 m screened/armoured
Yes
15 m screened/armoured
No
3 x 200 V version with 1A RFI
filter (R4: For use with RCD)
Yes
20 m screened/
armoured
Yes
20 m screened/armoured
Yes
7 m screened/armoured
No
3x480 V version with 1A+1B
RFI filter
Yes
50 m screened/
armoured
Yes
50 m screened/armoured
Yes
25 m screened/armoured
No
1x200 V version with 1A+1B
RFI filter
1)
Yes
100 m screened/
armoured
Yes
100 m screened/
armoured
Yes
40 m screened/armoured
No
VLT 2880-2882 Emission
Industrial environment Residential, commerce and light industry
EN 55011 class 1A EN 55011 class 1B
Set-up Cable-borne
150 kHz-30 MHz
Radiated
30 MHz-1 GHz
Cable-borne
150 kHz-30 MHz
Radiated
30 MHz-1GHz
3x480 V version with 1B RFI
filter
Yes
50 m
Yes
50 m
Yes
50 m
No
Table 5.5 EMC Emission Compliance
1) For VLT 2822-2840 3x200-240 V, the same values apply as for the 480 V version with 1A RFI filter.
All about VLT 2800
Design Guide
MG27E402 Danfoss A/S © Rev. May/2014 All rights reserved. 133
5 5

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals