5.1.20 Generic EMC Standards / Product Standards
Standard/environment Industrial environment Residential, commercial and light industry
EMC Product Standard EN61800-3 EN61800-3
1st edition, 1996 Unrestricted Restricted Unrestricted Restricted
2nd edition, 2004 Category 3 Category 4 Category 1 Category 2
EMC Basic Standard, EN55011, Cable-
borne/Radiated
Class A2
EMC plan
1)
Class B Class A1
Generic EMC standards EN 61000-6-4 EN 61000-6-3
EMC Basis Standard, EN55011, Cable-
borne/Radiated
Class A Class B
1) Described in details in the EMC Product Standard. This category is among other things for complex installations (for instance IT supply
networks).
The following system results are achieved on a system consisting of a VLT
®
2800 frequency converter with screened/
armoured control cable, control box with potentiometer, screened/armoured motor cable and screened/armoured brake
cable as well as an LCP2 with cable.
VLT 2803-2875 Emission
Industrial environment Residential, commercial and light industry
EN 55011 class 1A EN 55011 class 1B
Set-up Cable-borne
150 kHz-30 MHz
Radiated
30 MHz-1 GHz
Cable-borne
150 kHz-30 MHz
Radiated
30 MHz-1 GHz
3x480 V version with 1A RFI
filter
Yes
25 m screened/
armoured
Yes
25 m screened/armoured
No No
3x480 V version with 1A RFI
filter (R5: For IT mains)
Yes
5 m screened/armoured
Yes
5 m screened/armoured
No No
1x200 V version with 1A RFI
filter
1)
Yes
40 m screened/
armoured
Yes
40 m screened/armoured
Yes
15 m screened/armoured
No
3 x 200 V version with 1A RFI
filter (R4: For use with RCD)
Yes
20 m screened/
armoured
Yes
20 m screened/armoured
Yes
7 m screened/armoured
No
3x480 V version with 1A+1B
RFI filter
Yes
50 m screened/
armoured
Yes
50 m screened/armoured
Yes
25 m screened/armoured
No
1x200 V version with 1A+1B
RFI filter
1)
Yes
100 m screened/
armoured
Yes
100 m screened/
armoured
Yes
40 m screened/armoured
No
VLT 2880-2882 Emission
Industrial environment Residential, commerce and light industry
EN 55011 class 1A EN 55011 class 1B
Set-up Cable-borne
150 kHz-30 MHz
Radiated
30 MHz-1 GHz
Cable-borne
150 kHz-30 MHz
Radiated
30 MHz-1GHz
3x480 V version with 1B RFI
filter
Yes
50 m
Yes
50 m
Yes
50 m
No
Table 5.5 EMC Emission Compliance
1) For VLT 2822-2840 3x200-240 V, the same values apply as for the 480 V version with 1A RFI filter.
All about VLT 2800
Design Guide
MG27E402 Danfoss A/S © Rev. May/2014 All rights reserved. 133
5 5