3.4.17 Relay Connection
See parameter 323 Relay output for programming of relay output.
Nr. 01 - 02 1 - 2 make (normally open)
01 - 03 1 - 3 break (normally closed)
WARNING
The cable jacket for the relay must cover the first row of control card terminals. Otherwise the galvanic isolation (PELV)
cannot be maintained, which could result in equipment damage and personal injury. Maximum cable diameter is 4 mm.
Illustration 3.35 Relay Connection
3.4.18
Switches 1-4
The dip switch is only on the control card with Profibus DP
communication.
The switch position shown is the factory setting.
Switches 1 and 2 are used as cable termination for the
RS-485 interface. If the frequency converter is located as
the first or last unit in the bus system, switches 1 and 2
must be ON. On the remaining frequency converters,
switches 1 and 2 must be OFF.
Switches 3 and 4 are not applied.
3.4.19
VLT Motion Control Tool MCT 10
Set-up Software
Connection to terminals 68-70 or Sub D:
PIN 3 GND
PIN 8 P-RS 485
PIN 9 N-RS 485
Installation Design Guide
MG27E402 Danfoss A/S © Rev. May/2014 All rights reserved. 55
3 3

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
Frequency50/60 Hz
EnclosureIP20
Input Voltage200-240V AC
Output Power Range0.37-2.2kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Communication InterfaceRS485
Operating Temperature-10°C to +40°C
Storage Temperature-25°C to +65 °C
Relative Humidity5 - 95% RH, non-condensing
Output Voltage0 - 100% of supply voltage