5.4 Mains Supply
5.4.1 Mains Supply 1x220-240 V/3x200-240 V
According to international
standards
Type 2803 2805 2807 2811 2815 2822 2822
PD2
2840 2840 PD2
Output current I
INV.
[A] 2.2 3.2 4.2 6.0 6.8 9.6 9.6 16 16
(3x200-240V)
I
MAX
(60 s) [A] 3.5 5.1 6.7 9.6 10.8 15.3 10.6 25.6 17.6
Output power
(230 V)
S
INV.
[KVA] 0.9 1.3 1.7 2.4 2.7 3.8 3.8 6.4 6.4
Typical shaft
output
P
M,N
[kW] 0.37 0.55 0.75 1.1 1.5 2.2 2.2 3.7 3.7
Typical shaft
output
P
M,N
[HP] 0.5 0.75 1.0 1.5 2.0 3.0 3.0 5.0 5.0
Max. cable
cross-section,
motor
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6
Input current I
L,N
[A] 5.9 8.3 10.6 14.5 15.2 - 22.0 - 31.0
(1x220-240 V) I
L,MAX
(60 s) [A] 9.4 13.3 16.7 23.2 24.3 - 24.3 - 34.5
Input current I
L,N
[A] 2.9 4.0 5.1 7.0 7.6 8.8 8.8 14.7 14.7
(3x200-240 V) I
L,MAX
(60s) [A] 4.6 6.4 8.2 11.2 12.2 14.1 9.7 23.5 16.2
Maximum cable
cross-section,
power
[mm
2
/AWG]
1)
4/10 4/10 4/10 4/10 4/10 4/10 4/10 4/10 16/6
Maximum pre-
fuses
IEC/UL
2)
[A]
20/2
0
20/20 20/20 20/20 20/20 20/2
0
35/35 25/25 50/50
Efficiency
3)
[%] 95 95 95 95 95 95 95 95 95
Power loss at
100% load
[W] 24 35 48 69 94 125 125 231 231
Weight [kg] 2.0 2.0 2.0 2.0 2.0 3,7 6.0 6.0 18.50
Enclosure
4)
type IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20/
NEMA 1
Table 5.13 Mains Supply 1x220-240 V/3x200-240 V
1) American wire Gauge. Maximum cable cross-section is the largest cable cross section that can be attached to the terminals. Always observe
national and local regulations.
2) Use Type gG pre-fuses for installation according to IEC rules. To maintain UL/cUL, use pre-fuses of the type Bussmann KTN-R 200 V, KTS-R 500 V
or Ferraz Shawmut, type ATMR (maximum 30 A). Place the fuses for protection in a circuit that is capable of supplying a maximum of 100,000
amps RMS (symmetrical), 500 V maximum.
3) Measured using a 25 m screened/armoured motor cable with a rated load and rated frequency.
4) IP20 is standard for VLT 2805-2875, whereas NEMA 1 is an option.
All about VLT 2800 Design Guide
146 Danfoss A/S © Rev. May/2014 All rights reserved. MG27E402
55

Table of Contents

Other manuals for Danfoss VLT 2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 2800 and is the answer not in the manual?

Danfoss VLT 2800 Specifications

General IconGeneral
BrandDanfoss
ModelVLT 2800
CategoryDC Drives
LanguageEnglish

Related product manuals